Dimensjoner

  • Lengde(mm):
    3647
  • Bredde(mm):
    2434
  • Høyde(mm):
    2922
  • Vekt (kg):
    8400
  • Løfting/ Transport:
    12' Offshore container with forklift channels and lifting slings. DNV 2.7-1
  • Sertifikater / Serie Nr.:
    FMW9039/11/97

Byggeår

  • Byggeår:
    1998

Bruksområde / Sertifisering

  • Onshore/offshore:

    Offshore

  • Standard:
    Norsok Z-015 - Unclassified area (80 dBa)

Flow / Trykk / Volum

  • Boiler:
    Clayton E-185 (Ser. No: BG 47044-B 6243)
  • Gnistfanger:

    DNV certified. (Ref. cert./Ser. no. : SU-14b / GF-02)

    Dimension : L 2820mm W 1000mm H 1570mm. Weight : 560 kg

    Lifting/Transport : 2-leg chain sling

  • Maksimum Effect (kW):
    1850
  • Maks. steam produksjon (kg/hr):
    2900
  • P-max (bar):
    10
  • P-max (PSI):
    145
  • Maks Steam temperatur (Gr.C):
    184
  • Fødevannstank volum (ltr):
    1240
  • Diesel tankvolum (ltr):
    715
  • Dieselforbruk (ltr/time):
    210

Tilkoblinger

  • Tilkopling inn:
    1" offshore claw coupling
  • Tilkopling ut:
    2” Steamcoupling Boss Spud (New type)

Filter

  • Filterhus inn/retur (type):
    Feedwater inlet: HECO 899014001 Diesel inlet: RACOR 500 FG
  • Filterelement inn/retur (type):
    Feedwater inlet: PX 2010 Diesel inlet: PF-598-30

Strømforsyning

  • Sikring (antall):
    1
  • Sikring (A):
    63
  • Strøm tilkopling 1:
    400-480 V (main)
  • (Hz):
    50/60
  • (A):
    63
  • Strøm tilkopling 2:
    690 V (main)
  • (Hz):
    50/60
  • Strøm tilkopling 3:
    230 V (Fire,gas,light,heat)
  • (Hz):
    50/60

Annen informasjon

  • Utstyr / Funksjoner:

    High fire steam production : 2900 kg/hour @ 7,5 bar

    Low fire steam production : 1450 kg/hour @ 10 bar

    - The water consumption at full effect is 20% higher than the steam production.

    Sprinkler system : Swordsman foam system.

    Fire, gas central : Ceag Eexde IIC T5 Ser. no. J0115/D/S

    Ignition source connection and pressure relief steam if:

    -10% gas alarm (Detector mounted near air inlet).

    - Flame detector, fault and emergency shut-down.

    - Emergency shut-down on the outside of the container and the interior of the container.

    - Shut down/Emergency shut-down from control room. NAS/ESD

    Other safety functions :

    - Flame detector on burner.

    - Ring thermostat on coil.

    - Level monitor in feed water tank.

    - Temperature monitor steam 225˚C

    - Max. surface temperature is 200ºC.

    - Max. exhaust temperature is 300ºC.

    - Fire, gas, fault

    Signal SCR:

    - Shut-down NAS/ESD